Agilent Technologies DP111 Spécifications Page 181

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 452
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 180
Section 4 Operation AC 800M Controller (PM8xx)
3BSE036351-510 A 181
Switches and Push buttons
Connectors
Table 21. PM8xx – Switches and Push buttons
Marking Type Function
INIT Manual Push
button
Initiates
1. Cold Restart if INIT is held less than 2.5
seconds.
2. Controller Reset if INIT is held more than
3 seconds.
If INIT is pushed on the Primary CPU in
redundant configuration a switchover to the
backup CPU will be initiated.
Table 22. PM8xx/TP830 and PM891 – Connectors
Marking Function
L+
L–
SA
SB
External Power Supply Connection
+24 V DC supply
0 V
Redundant Power Supply monitoring input
Redundant Power Supply monitoring input
SH
B+
B–
External Battery Connection
Shield (Screw Connector)
Battery Positive (Screw Connector)
Battery Negative (Screw Connector)
Tx
Rx
ModuleBus Connection
Data Transmission Port (Optical)
Data Reception Port (Optical)
Note – Duplex or Simplex optical cables may be used.
MODULEBUS
(1)
Provides expansion of I/O unit capability.