89
66000 MPS mainframe. For applica-
tions with a broader range of power
requirements, one 66000 mainframe
can be connected with up to eight of
the 6640, 6650, 6670, 6680, 6690 or
6030 series of system power sup-
plies. This solution provides power
ranges from 150 watts to 5000 watts
at one primary GPIB address.
Output connections
System assembly is simplified
thanks to a quick-disco nnect connec-
tor assembly on each module. Once
your wires are connected to the
load, the connector design permits
the modules to be removed from
the front of the mainfram e without
disconnecting cabling or removing
the mainframe from the rack. One
connector assembly is shipped with
each module.
Output sequencing
Increase test throughput by using
the output sequencing feature
of the 66000 MPS. This powerful
feature allows you to download
up to 20 voltage, current, and
dwell-time paramete r sets per out-
put. This sequence can be paced by
the programmed dwell times. As an
alternative, triggers can be used to
step through the output list. The
output sequences can be executed
without controller intervent ion,
thereby increasing overall test
system through put. More detai led
information on the triggering and
output sequencing capabilities can
be obtained by o rdering the 66000
Modular Power System Product Note
(p/n 5091-2497E).
Modular Power System
1200 W per mainframe GPIB (Continued)
Sp ecifica ti on s
(at 0° to 55°C unless
otherwise specified)
66101A- 66101A- 66102A- 66103A- 66103A-
J03 J05 J05 J01 J02
Special order Special order Special order Special order Special order
option option option option option
Output ratings at 40°C
Output voltage 5.7 V 12 V 15 V 37 V 40 V
Output current 20 A 12 A 10 A 4.5 A 3.6 A
Maximum power 114 W 144 W 150 W 167 W 144 W
Programming accuracy
at 25°C ±5°C
Voltage 0.03% + 2.5 mV 5 mV 8 mV 13 mV 15 mV
Current 0.03% + 8 mA 6 mA 4 mA 2 mA 2 mA
Readback accuracy
(via GPIB keyboard display
at 25°C ±5°C)
Voltage 0.02% + 2 mV 3 mV 5 mV 8 mV 9.2 mV
Current 0.02% + 8 mA 6 mA 4 mA 2 mA 2 mA
Ripple and noise (20 Hz to 20 MHz)
Constant voltage rms 2 mV 3 mV 3 mV 5.3 mV 6 mV
peak-peak 5 mV 7 mV 7 mV 10.6 mV 11.5 mV
Constant current rms 10 mA 8 mA 6 mA 2 mA 2 mA
Line regulation
Voltage 0.5 mV 0.5 mV 0.5 mV 1 mV 1 mV
Current 0.5 mA 0.75 mA 0.5 mA 0.3 mA 0.3 mA
Load regulation
Voltage 1 mV 1 mV 1 mV 1 mV 1 mV
Current 1 mA 0.5 mA 0.3 mA 0.2 mA 0.2 mA
Transient response time Less than 1 ms for the output voltage to recover within 100 mV of its
previous level following any step change in load current up to 10 percent
of rated current
Supplemental Characteristics (Non-warranted characteristics determined by design
that are useful in applying the product)
Average resolution
Voltage 2 mV 3.6 mV 4.5 mV 11 mV 12 mV
Current 6 mA 4.6 mA 3.1 mA 1.4 mA 1.2 mA
OVP 45 mV 75 mV 90 mV 200 mV 230 mV
OVP accuracy 250 mV 375 mV 375 mV 850 mV 920 mV
More detailed specifications at
www.agilent.com/find/66000
High Performance DC Power Supplies speed and accuracy for test optimization
Application notes
66000 Modular Power System
Product Note
5988-2800EN
10 Practical Tips You Need to
Know About Your Power Products
5965-8239E
10 Hints for Using Your Power Supply
to Decrease Test Time
5968-6359E
Agilent DC Power Supplies
for Base Station Testing
5988-2386EN
Vue de la page 92
1 2 ... 88 89 90 91 92 93 94 95 96 97 98 ... 148 149

Commentaires sur ces manuels

Pas de commentaire