Appendix A Hardware Units SS822/SS823/SS832 Voting Unit (for Redundant Power Supply)
3BSE036351-510 A 387
Contact rating a.c. Max. 30 V and max. 0.5 A, resistive load
Contact rating d.c. Max. 60 V and max 0.3 A, 30 V max 0.5
A
resistive load
min. 1 mA at 5 V d.c.
Acceptable wire sizes 0.2 -1.5 mm
2
, 22 - 14 AWG
Recommended torque: 0.4 Nm
Table 123. Technical Data and Mounting Dimensions
Parameter SS832 Voter
Input current 10A per input
Rated output current 20 A
Mains/input voltage, nominal 2 x 24 V d.c.
Rated/input voltage 60 V d.c.
Heat dissipation 8.9 W at 10 A and 4.6 W at 5 A
Input to output voltage drop at max.
current
0,85 V
Maximum output current 25 A (Overload)
Ingress Protection IP20 according to EN60529, IEC 60529.
Max ambient temperature 55
o
C
(1)
Acceptable wire sizes Solid: 0.5 - 6 mm
2
, 20 - 10 AWG
Stranded: 0.5 - 4 mm
2
, 20 - 10 AWG
Recommended torque: 0.8 Nm
Table 122. SS832 Voting Unit - Supervision Data (Continued)
Supervision Data SS832